Protest 010 — BRT Station Waterproofing IED
Protest Timeline · ISS-010 · Dispute Stage · As of March 2026
Overview
WSDOT issued SL 9727-209 (December 3, 2025) as an Interpretive Engineering Decision (IED) under GP 1-03.5, requiring below-grade sheet-applied membrane waterproofing and watertight elevator pits at Brickyard West, East, and Canyon Park BRT stations. Skanska protested (LTR 287, December 5), supplemented (LTR 301, December 19), and filed a second supplement (LTR 310, December 31). WSDOT denied all claims (SL 9727-239, January 9, 2026). Skanska filed a Dispute Notification (LTR 331, January 23, 2026) and is proceeding with work while disputing.
Timeline
| Date |
Party |
Letter |
Description |
| 2025-12-03 |
WSDOT |
SL 9727-209 |
Interpretive Engineering Decision: below-grade sheet-applied membrane waterproofing and watertight elevator pits required at Brickyard West, East, and Canyon Park BRT stations |
| 2025-12-05 |
Skanska |
LTR 287 |
Notice of Protest 010 against waterproofing and elevator pit requirements. Triggering letter. |
| 2025-12-19 |
WSDOT |
SL 9727-221 |
Acknowledges Notice of Protest 010. Confirms Written Determination forthcoming. |
| 2025-12-19 |
Skanska |
LTR 301 |
Supplemental information. Claims inconsistency in WSDOT’s position. Proposes accepting Work as constructed (Hycrete-only approach). |
| 2025-12-31 |
Skanska |
LTR 310 |
Responds to SL 9727-221. Asserts that the spec as written would void the Hycrete warranty if membranes applied to existing substrate. Suggests DBIC to eliminate membrane requirement. |
| 2026-01-09 |
WSDOT |
SL 9727-239 |
Denies all claims. Suggests DBIC path for Sound Transit written approval. Clarification: if membrane applied to vertical surfaces, pit slab at Brickyard West need not be replaced. |
| 2026-01-23 |
Skanska |
LTR 331 |
Dispute Notification per RFP Section 1-04.5(1). Will proceed with work as directed while continuing to dispute. Dispute stage begins. |
Procedural Status
| Step |
Status |
Notes |
| Notice of Protest |
Complete |
LTR 287 (Dec 5, 2025) — 2 days after SL 9727-209. Timely. |
| WSDOT Acknowledgment |
Complete |
SL 9727-221 (Dec 19, 2025) |
| Supplemental Submissions |
Complete |
LTR 301 (Dec 19) and LTR 310 (Dec 31) |
| WSDOT Written Determination |
Complete |
SL 9727-239 (Jan 9, 2026) — protest denied |
| Dispute Notification |
Complete |
LTR 331 (Jan 23, 2026) — 14 days from SL 239. Timely. |
| DRB Referral |
Pending |
Awaiting written Dispute Referral from Skanska per Section 1-04.5(1).18 |
Key Contract Provisions
| Section |
Purpose |
| GP 1-03.5 | IED authority — WSDOT may issue its own IEDs; IEDs do not create cost/time entitlement |
| S07 07 10 00 | Membrane waterproofing requirements at below-grade elements |
| S07 07 13 53 | Elastomeric sheet membrane waterproofing specification |
| S07 03 15 13 Part 2.01.C | Butyl-strip waterstops in Hycrete concrete require exterior membranes |
| S07 14 24 00 | Hydraulic elevator pit must be watertight/sealed before installation |
| DCM 25.4.1.J | Elevator pits must prevent groundwater entry and fluid release |
| GP 1-03.2 | Order of Precedence — Technical Requirements control over building code |
| GP 1-03.7 | Reviews/approvals do not constitute waivers |
| GP 1-04.4(5)(b) | Design review corrections are not eligible for change orders |